Singapore Government
Link to AGC Website
Home | Search | Browse | Results | My Preferences
 
Contents

Part I PRELIMINARY

Part II PACKAGES

Part III TRANSPORT

Part IV STORAGE OF PETROLEUM IN QUANTITIES EXCEEDING 5 CASES BUT NOT EXCEEDING 12½ CASES

Part V STORAGE OF PETROLEUM IN QUANTITIES EXCEEDING 12½ CASES BUT NOT EXCEEDING 100 CASES OR EXCEEDING 182 LITRES BUT NOT EXCEEDING 3,637 LITRES

Part VI STORAGE OF PETROLEUM IN QUANTITIES EXCEEDING 100 CASES BUT NOT EXCEEDING 400 CASES

Part VII QUANTITIES OF PETROLEUM EXCEEDING 400 CASES OR PETROLEUM IN BULK EXCEEDING 3,637 LITRES

Part VIII STORAGE OF DANGEROUS PETROLEUM IN SMALL QUANTITIES FOR PRIVATE USE

Part IX STORAGE OF DANGEROUS PETROLEUM IN QUANTITIES NOT EXCEEDING 90 LITRES

Part X STORAGE OF DANGEROUS PETROLEUM IN QUANTITIES EXCEEDING 90 LITRES BUT NOT EXCEEDING 227 LITRES

Part XI STORAGE OF DANGEROUS PETROLEUM IN QUANTITIES EXCEEDING 227 LITRES BUT NOT EXCEEDING 2,270 LITRES

Part XII STORAGE OF DANGEROUS PETROLEUM IN QUANTITIES EXCEEDING 2,270 LITRES

Part XIII STORAGE OF DANGEROUS PETROLEUM IN UNDERGROUND TANKS FOR PURPOSES OF RETAIL TRADE OR PRIVATE CONSUMPTION

Part XIV STORAGE OF DANGEROUS PETROLEUM IN TANKS IN QUANTITIES EXCEEDING 9,092 LITRES

Part XV GENERAL

Legislative History

 
Slider
Left Corner
Print   Permalink
On 19/05/2013, you requested for the version in force on 19/05/2013 incorporating all amendments published on or before 19/05/2013. The closest version currently available is that of 25/03/1992.
PART X
STORAGE OF DANGEROUS PETROLEUM IN QUANTITIES EXCEEDING 90 LITRES BUT NOT EXCEEDING 227 LITRES
Storage
35.  Before the Director grants a licence for the storage of dangerous petroleum in quantities exceeding 90 litres, but not exceeding 227 litres, the applicant shall provide within his premises in such a position as may be approved by him one or more storage bins constructed of brickwork of a thickness of not less than 11 centimetres rendered inside with cement of a thickness of not less than 1.3 centimetres and shall be in measurement 0.9 metre, by 0.9 metre, by 0.7 metre, fitted with an hinged iron lid on the top of not less than 3 millimetres thick.
Storage only in approved positions and receptacles
36.  The dangerous petroleum shall be stored in the approved positions or receptacles only and in no other part of the premises.
Naked lights prohibited
37.  In premises licensed for the storage of 90 litres or more, no fire or cooking-place or artificial light shall be used within 4.5 metres of the storage receptacle.
Transfer of dangerous petroleum in day light
38.  No drum or tin containing dangerous petroleum shall be broached or opened nor shall any dangerous petroleum be drawn off or changed from one receptacle to another at any time under circumstances where the use of artificial light is necessary.
Soldering works prohibited
39.  The soldering of drums or tins containing dangerous petroleum or the application thereto of any operation in which fire or heat is used is prohibited on the licensed premises.